UPA-100
Circuit Breaker Accessory, ATC UPA-100 Series Circuit Breaker/Main Disconnect/UPA Flashes
Product Information
Product Overview
UPA-100 series universal power alert reduces the risk of electrical arc flash by pre-verifying the electrical isolation from outside of a control panel. Hard wired to the circuit breaker or main disconnect, the UPA flashes whenever voltage is present. Engineered with redundant circuitry, the power alert is powered by the same voltage that it indicates. Operation: The eight-detector UPA-100 visually alerts to the presence of dangerous AC or DC (Stored Energy) potentials occurring between any combination of the four monitored input lines (L1, L2, L3, GND). Two LED indicator is assigned to each input line and are designated “+” and “-”. UL Listed under UL File Number E55826. UPA-100C UNIVERSAL POWER ALERT CAT III CAT IV.
- Detects single or 3-phase AC and DC voltage or stored energy
- Redundant circuitry, verification of zero energy in a panel
- Fits 1-1/4" conduit knock-out
- 40 to 600VAC, 50/60/400Hz, (LINE-TO-LINE or LINE-TO-GND) AC single or 3-phase operational range
- 30 to 1000VDC, (LINE-TO-LINE or LINE-TO-GND) DC or stored energy
- 750VAC/1000VDC (LINE-TO-LINE or LINE-TO-GND) maximum rated voltage
- 29VAC 3-Phase, 40VAC Single-phase 27VDC (TYP Cutoff) detection thresholds
- 1.2W at 750VAC (approx.) power consumption, (4) 8 ft, 18 AWG 1000V, UL-1452 termination
- NEMA 4X 105°C PVC, totally encapsulated for environment protection enclosure
- Operating temperature range from -20° to +55°C